Chilled & Condenser Water Pipe Sizing
Enter your cooling load and chiller plant data to get the chilled-water and condenser-water flows and the recommended Schedule-40 pipe and header sizes — selected to ASHRAE / SNI velocity and friction limits. Related: see the chiller plant in 3D.
Enter the design flow straight off your equipment schedule. The header carries the total flow, each branch carries one unit, and a pump branch carries the total shared across the duty pumps.
Chilled water — evaporator side
Condenser water — cooling-tower side
Advanced limits
Please enter all values, then press Calculate.
| Segment | Flow | Pipe size | Velocity | Friction |
|---|
How it sizes: each segment's pipe is the smallest Schedule-40 size whose velocity ≤ the limit and friction ≤ the limit (Hazen-Williams). Branch = one unit's flow, header = all units combined, pump branch = total ÷ duty pumps. Indicative only — confirm against full pump head, fittings and the equipment selected. Need it built? Talk to our engineering team.
Advanced limits
Please enter all values, then press Calculate.
| Pipe | Flow | Size | Velocity | Friction |
|---|
Method: water flow = load ÷ (4.187 × ΔT). Pipe size is the smallest Schedule-40 DN whose velocity ≤ the limit and friction ≤ the limit (Hazen-Williams). Defaults follow ASHRAE / SNI 6390 practice — ≤1.2 m/s for small pipes, ≤400 Pa/m friction. Indicative only — confirm against a full hydraulic design, fittings, pump head and the equipment selected. Need it sized and built? Talk to our engineering team.